Servo Voltage Stabilizer 3 Phase

Servo Voltage Stabilizer 3 Phase Exporters in Zambia
Description :
Servo Voltage Stabilizer is commonly observed that, AC main supply is never 230 Volt or 415 Volt, but varies from 150 Volt – 300 volt and 300 Volt – 500 Volt. The difficulties caused by them are well known, such as Over Load Condition, Line Losses, Poor Power Factor and several other reasons. The three phase servo voltage stabilizer helps in constant voltage which is required to load is never constant, but in fluctuation manner. It is observed that during the daytime, the voltage is quiet low and during the night the Voltage is high then the normal. This fluctuation in supply system results frequent breakdown, low production and also loss of energy. The performance of any electrical equipment is optimum at its rated voltage. Both over / under voltages are harmful for the system. The under voltage reduces efficiency whereas the over voltage shortens the life and the best product which saves from such issues is the 3 phase servo controlled voltage stabilizer.
The power agencies insist the consumer to fix the capacitor to improve power factor to get better results in power saving. But Voltage is far more important factor to save the power loss. In case of very Low / High voltages, the telecom systems are powered by DG sets. Our Line Conditioner Unit meets the requirement of input voltage variation from 110V – 280V (Single phase) and 300V – 500V (Three phase). 240V – 500V is also available on demand. In India, there are large voltage variations in the mains power supply. To overcome this problem, we are offering Line Conditioner Unit the 3 phase servo controlled voltage stabilizer and the 3 phase servo stabilizer for home.
Technical Specifications :
Parameter: | Single Phase Unit: | Three Phase Unit |
Rating: | 2 KVA to 50 KVA | 6 KVA to 2000 KVA |
Input Voltage Range: | a) 207V - 280V b) 180V-280V c) 160V - 280V d) 140V - 280V |
a) 360V - 470V b) 340V-470V c) 300V - 470V d) 250V-470V |
Nominal Output Voltage: | 230V | 400V |
Output Voltage Accuracy: | ± 1% | ± 1% |
Line Frequency Variation | 47Hz-53Hz | 47Hz-53Hz |
Effect of Power Factor | None | None |
Wave Form Distortion | None added | None added |
Control | Digital/Analogue | Digital/Analogue |
Response Time | 10 ms. | 10 ms. |
Voltage Correction Rate Air Cooled Oil Cooled |
25V/Sec 15V/Sec |
40V / Sec 25V/Sec. |
LCD Display (20 x 2 matrix) | LCD Display (20 x 2 matrix) | |
Log Book Memory (Non- volatile) | No. of Hrs. of operation on mains. Peak Current demand. Nos. of Abnormal High Voltage cut-off events. Nos. of Abnormal Low Voltage cut-off events. No. of Hrs. of operation on DG. |
|
Programmable Features (Through 2-parallel way resettable passwords) |
HV cut-off set. LV cut-off set. O/L trip set. Time delay set Operating mode (auto/manual) |
|
Cooling 1. Air Cooled 2. Oil Cooled |
2 KVA to 40 KVA & above 5 KVA to 1000 KVA & above |
|
Efficiency | 97% | |
Protection | a) Automatic Switch-Off against: • Under/Over-Voltage • Over-Load & Short Circuit • Single Phasing |
|
Surge Protection | Class C Type Secondary Surge Protection |